Hotline  027-81314188

Products
Your location:Home > Products > Cable and line testing equipment
YNDS-H cable identification instrument
YNDS-H cable identifier is an instrument used to identify a specific cable from a bundle of cables. It can identify power-off cables as well as live cables...
Reminder: For product purchase, technical maintenance and other services, please call!
Product Introduction

YNDS-H cable identifier is an instrument used to identify a specific cable from a bundle of cables. It can identify power-off cables as well as live cables, which meets the multiple requirements for cable identification at power construction sites.

The identification instrument is mainly composed of a transmitter host, a receiver host, a transmitter connection, a transmitter caliper and a flexible measuring coil. The design of the identification instrument is more compact than the previous generation product, and it is convenient to carry. It has the following characteristics:

1) The transmitter is powered by a high-energy lithium battery and does not require on-site 220V power access. It is easy to use, and has a compact design, low power consumption, long power supply time, and multi-level power indication.

2) The receiving host adopts color LCD LCD display, accurate power prompt, synchronous display signal direction, amplitude, interval as the effective judgment basis, and retains multiple signals on the time axis, through continuous effective signals to more accurately determine the to-be-identified cable.

3) The flexible measuring coil is used for cable identification, which solves the problem that the traditional receiving calipers cannot be stuck into the cable to be identified due to the congestion and overlapping of the cables in the power field.

4) Equipped with transmitting calipers, the function of live identification is realized through caliper coupling, so that one machine can be used for multiple purposes.

5) ABS high-strength protective box, which effectively protects the instrument, is convenient for transportation and adapts to the harsh environment of the construction site.

Performance characteristics

The transmitter host couples the regular pulse signal to the armor shielding layer of the cable to be identified through a clamp, and forms a current loop through grounding at both ends, so both ends of the cable to be identified must be reliably grounded, because the current signal coupled to the cable is more than direct injection The current signal is much smaller, so it is necessary to increase the gain level of the receiving host during power-on recognition. The same as power failure, when multiple consecutive signals consistent with the direction, amplitude and interval of the injected signal are received, it is the target to be recognized. cable.

Technical Parameters

2.2.2 Dimensions (length × width × height)

Case: 520mm×350mm×170mm

2.2.3 Launch host

Charging voltage: DC5V

Power consumption: ≤3W

Working hours: ≥12h

Signal interval: ≈2 seconds

Launch caliper inner diameter: 125mm

Ambient temperature: -35℃~+55℃

Environmental humidity: ≤95%RH

2.2.4 Receiving host

Charging voltage: DC5V

Power consumption: ≤1W

Recognition method: direction, amplitude, interval, triple judgment basis

Loop resistance range: power failure-ground loop resistance ≤ 500Ω

Charged--ground loop resistance ≤200Ω

Working hours: ≥12h

Ambient temperature: -35℃~+55℃

Environmental humidity: ≤95%RH

 

Product details
  • Whole machine
  • Receiving host

  • Launch host
Test Report

Our company's products are produced in strict accordance with international standards, national standards, and industry and enterprise standards. They have passed professional inspections by national, provincial and municipal electric power research institutes, measurement centers and electric power authorities, and fully passed the ISO9001 international quality management system certification. GB/T19001-2008 quality management system requirements, GB/T24001-2004 environmental management system requirements, GB/T28001-2011 occupational health and safety management system requirements.

          

After-sales service
With your support and trust, in order to protect your interests, enable you to get better and higher-quality services, and to establish a good corporate image for our company, we are guided by the principle of "pursuing high quality in everything, and customer satisfaction". We will provide you with relevant services in strict accordance with contract requirements and product technical specifications to meet user needs, and solemnly promise you with the principle of "enthusiasm for pre-sales, in-sales, and after-sales services":
  • Pre-sale commitment

    Warmly welcome calls and visits
    Provide fast and professional response
    Timely, serious and reasonable quotation
  • Commitment in sale

    Strictly execute the contract
    Professional technical training
    Timely and regular return visits
  • After-sales service

    Punctual delivery with quality and quantity
    Take information feedback seriously
    Free lifetime technical consultation
Copyright © Wuhan Yueneng High Test Power Equipment Co.,Ltd. http://www.whyngc.com All Rights Reserved    Website productionSanjin.net    鄂ICP备16014120号-2