YNLB-II Leakage Protector Tester is mainly used to test the leakage action current, the leakage non-action current and the leakage action time of the leakage protector. The test current is 0-500mA divided into ten gears, and the time test range is 0-799ms, 16 characters This tester is hand-held, small in size, light in weight and easy to carry. It is a test instrument for on-site or indoor detection of various leakage protectors.
The YNLB-II leakage protector tester is equipped with a "manual/automatic" switch button. The LCD screen directly above displays "AUTO 000ms (Note: AUTO=automatic), which is the automatic detection state. When the "shift" button is used to select During the rated operating value test, if the trip is not possible, the test value will be automatically increased by one level after 1 second. Continuous testing until the leakage protector is tripped and disconnected. At this time, the red light on the left vertical row corresponds to the actual level. Leakage action current value, the LCD screen directly above displays "AUTO xxxms (xxx is the action time value of the corresponding current gear).
1. Rated voltage: AC220V/380V;
2. Test line voltage: below AC250V;
3. Leakage current classification: 15, 30, 50, 75, 100, 150, 200, 250, 300, 500mA, a total of ten levels;
4. Test time range of leakage action: 0-799ms;
5. Leakage current accuracy: level 1;
6. Action time display accuracy: 0.5% (±2 characters);
7. Operating environment temperature: 0℃~40℃;
8. The relative humidity of the operating environment: <85%;
9. Dimensions: 195×101×42mm.
-
Host
- Test line
Our company's products are produced in strict accordance with international standards, national standards, and industry and enterprise standards. They have passed professional inspections by national, provincial and municipal electric power research institutes, measurement centers and electric power authorities, and fully passed the ISO9001 international quality management system certification. GB/T19001-2008 quality management system requirements, GB/T24001-2004 environmental management system requirements, GB/T28001-2011 occupational health and safety management system requirements.
-
Pre-sale commitmentWarmly welcome calls and visits
Provide fast and professional response
Timely, serious and reasonable quotation -
Commitment in saleStrictly execute the contract
Professional technical training
Timely and regular return visits -
After-sales servicePunctual delivery with quality and quantity
Take information feedback seriously
Free lifetime technical consultation