The transformer on-load tap changer tester is a high-voltage test equipment according to the standard of the electric power industry of the People’s Republic of China. It is designed according to the general technical conditions DL/T846 and 8-2004. It can meet the requirements of the "Power Equipment Handover and Preventive Test Regulations". The action sequence of the on-load tap-changer, the measurement switching time and other requirements. It can realize accurate measurement of the on-load tap-changer's transition time, transition waveform, transition resistance, three-phase consistency and other parameters. It is an ideal equipment for testing on-load tap-changers. (The user is an on-load switch that adjusts the capacity, please inform in advance)
①. Test Y0 Y △ transformer, the resistance value is displayed directly without conversion;
②. Humanized data analysis, which can automatically find out the faults in the waveform and mark them;
③. The display of the waveform is to automatically adjust the resistance value and the amplitude of the time according to the sampled data;
④. △-type transformers can show three phases;
⑤. It can be tested with or without winding;
⑥. The four-terminal wiring method provides high-precision resistance measurement without wire compensation;
⑦. Continuous testing can be performed in the middle of the test, saving the time of transformer power outage;
⑧ The instrument can survive word reports, which is convenient for data management and query;
⑨. The instrument is controlled by a small computer, with an external 800×480 color LCD touch screen, a high-speed printer, and an external mouse, which is easy to operate;
⑩. 1000 sets of data can be automatically saved inside the instrument, or it can be saved with an external USB flash drive.
①. Three-phase constant current source charging, charging current: 3A/1A gear; 0.6A/0.2A gear
②. Port voltage: 24V
③. Transition resistance range: 100Ω
④. Transition resistance measurement range: 1A range: 0.4Ω~20Ω 0.2A range: 10Ω~100Ω
⑤. Waveform recording time length: 300ms
⑥. Sampling rate: 30k
⑦. Time resolution: 0.1ms
⑧. Resistance resolution: 0.1Ω
⑨. Accuracy: Transition resistance: ±5% of reading ±0.1Ω Transition time: ±0.5% of reading ±0.2mS
⑩. Operating temperature: -10~40℃ Relative humidity: <85%RH
- Overall
- Host
-
Panel
-
Screen
Our company's products are produced in strict accordance with international standards, national standards, and industry and enterprise standards. They have passed professional inspections by national, provincial and municipal electric power research institutes, measurement centers and electric power authorities, and fully passed the ISO9001 international quality management system certification. GB/T19001-2008 quality management system requirements, GB/T24001-2004 environmental management system requirements, GB/T28001-2011 occupational health and safety management system requirements.
-
Pre-sale commitmentWarmly welcome calls and visits
Provide fast and professional response
Timely, serious and reasonable quotation -
Commitment in saleStrictly execute the contract
Professional technical training
Timely and regular return visits -
After-sales servicePunctual delivery with quality and quantity
Take information feedback seriously
Free lifetime technical consultation