YNBC-T special transformer transformation ratio tester is the second generation of transformation ratio test equipment launched by our company in 2012. It can be used for three-phase transformer testing of power systems, and is especially suitable for testing Z-winding transformers, rectifier transformers and balance transformers. The instrument uses a large-screen LCD display, full Chinese menus and print output of Chinese characters. It has a friendly man-machine interface, complete functions and easy operation. It is used by power systems, transformer manufacturers and railway electrical systems to perform transformer ratio, group, polarity, and The ideal instrument for angle testing.
1. The instrument comes with a lithium battery, and the transformation ratio test can be carried out without an external power supply on site, and at least 100 transformers can be tested on a single charge;
2. The instrument integrates single-phase and three-phase standard power supplies with stable amplitude and constant phase.
3. The internal standard power supply has large output power and 5A output, which is especially suitable for low-voltage transformer testing and semi-finished product turns testing in the manufacturing process of CT and PT.
4. Accurately and quickly test the turns ratio, turn ratio error and phase difference of current transformer (CT) and voltage transformer (PT).
5. Test single-phase or three-phase transformers, suitable for Scott, reverse Scott and balance transformer tests of Z-winding transformers, rectifier transformers and railway electrical systems.
6. The test accuracy is high. The instrument adopts 16-bit high-precision AD and high-speed DSP processor, which effectively guarantees the measurement accuracy and anti-interference ability.
7. The instrument adopts non-partial discharge voltage regulation output, and the voltage regulation and measurement speed are fast. It only takes 5 seconds to complete the boost and test;
8. The instrument automatically judges the rated transformation ratio of the current tap: When testing a multi-tap transformer, you only need to enter the voltage regulation ratio of the tap switch once to perform the test without entering the current tap number, which greatly improves work efficiency.
9. Internal overcurrent protection and wiring check function.
10. Large 320x240 screen, high-brightness LCD display, full Chinese character menu and operation prompts to realize friendly man-machine dialogue. Rotating the mouse makes the operation easier.
11. Comes with a real-time electronic clock, which automatically records the date and time of the test, which is conducive to the preservation and management of the test results.
12. Panel thermal printer can quickly print test results on site.
13. The data has the functions of power-off storage and browsing, can store 1000 sets of experimental results, and can transmit data online with the computer.
1. Environmental conditions
Temperature: -5°C~40°C
Relative humidity: <95% (25°C)
Altitude: <2500m
External interference: no strong vibration, no strong electromagnetic field
Power supply: 160VAC~280VAC, 45Hz~55Hz
2. Measuring range
Test range of transformation ratio: 0.5~10000
Group test range: 1~12
Angle difference test range: 0~360°
3. Test accuracy
Measurement accuracy of transformation ratio: +0.1% (0.5~1000)
+0.2%(1001~2000)
+0.5%(2001~4000)
+1%(4001~10000)
Angle difference measurement accuracy:: 30`
4. Insulation strength
The insulation resistance of the voltage and current input terminals to the chassis is ≥100MΩ.
The power frequency is 2KV (effective value) between the input end of the working power supply and the shell, and the experiment lasted 1 minute.
- Host
-
Panel
-
Screen
-
Printer
Our company's products are produced in strict accordance with international standards, national standards, and industry and enterprise standards. They have passed professional inspections by national, provincial and municipal electric power research institutes, measurement centers and electric power authorities, and fully passed the ISO9001 international quality management system certification. GB/T19001-2008 quality management system requirements, GB/T24001-2004 environmental management system requirements, GB/T28001-2011 occupational health and safety management system requirements.
-
Pre-sale commitmentWarmly welcome calls and visits
Provide fast and professional response
Timely, serious and reasonable quotation -
Commitment in saleStrictly execute the contract
Professional technical training
Timely and regular return visits -
After-sales servicePunctual delivery with quality and quantity
Take information feedback seriously
Free lifetime technical consultation